Test Operation
9) Electronic Expansion Valve – EVI (EVI EEV)
What to inspect: Outdoor unit's EVI EEV operation
Error code: None ("NG" is only indicated in the result report)

of the EVI EEV

Precautions


Take corrective measures.
Take corrective measures.
Take corrective measures.
Replace the coil.
Replace the Hub PBA.
Does the result

indoor unit's thermistors are properly
functioning?
Is the EVI EEV
connector properly connected
to the PBA?
Are the thermistors
at the entrance and exit of the EVI attached
to the correct positions?
Is the coil
of the EVI EEV properly
functioning?*
Is the output
signal of the EVI EEV terminal on the Hub PBA
normal?*
Replace the EVI EEV*.
Perform Auto Trial Operation again.
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Connection diagram
Operation voltage
(VDC)
Phase-to-phase

Orange
Red

Black
Blue
12±2.0
Blue – Orange
Blue – Red

Blue – Black
92 ± 7.4
* It is possible to inspect the output signal, using a separate EVI EEV and
the vacuum mode.
* Replace it if the NG is still found after an additional Auto Trial Operation.
9-1 Auto Trial Operation (cont.)
9-1-3 How to resolve NG items (cont.)