Product Specications
2-16 Samsung Electronics
TYPE
DVM S
Model AM140FXVAGH AM160FXVAGH
Mode HP HP
Power Ø,V,Hz 3/AC380~415/50 3/AC380~415/50
Capacity
Horse Power HP 14 16
Capacity
kW 40.0 45.0
btu/h 136,000 153,000
Heating
kW 45.0 50.0
btu/h 153,000 170,000
Power
Power Input
(Nominal)
Cooling 1)
kW
8.90 11.00
Heating 2) 9.50 11.50
Current Input
(Nominal)
Cooling 1)
A
14.30 17.60
Heating 2) 15.20 18.40
Running
Current
Cooling A 14.30 17.60
Heating A 15.20 18.40
Max. A 25.00 32.00
Power
Consumption
Cooling kW 8.90 11.00
Heating kW 9.50 11.50
MCA / MFA A 31.3 / 40 40 / 40
COP
Nominal Cooling - 4.49 4.09
Nominal Heating - 4.74 4.35
ESEER (HP) 7.02 6.78
Compres-
sor
Model - DS-GB066FA**** DS-GB052FA****
Type INV x1 INV x2
Output kW 5.80 4.7 x2
Lubricant
Type - FVC68D FVC68D
Charging cc 3,900 6,200
Refrigerant
Type - R410A R410A
Factory Charging kg 7.7 7.4
FAN
Type - Propeller + BLDC Propeller + BLDC
Motor Output W 630 x 2 630 x 2
Airow rate
/min
226 250
Pipe
Piping
Connections
Liquid
Ø,mm 12.70 12.70
Ø,inch 1/2" 1/2"
Gas
Ø,mm 28.58 28.58
Ø,inch 1 1/8" 1 1/8"
Dis. Gas
Ø,mm 19.05 22.22
Ø,inch 3/4" 7/8"
Installation
Limitation
Max.Length m 200(220) 200(220)
Max.Height m 110(40) 110(40)
Cable
Main Power(Below/about20m) mm2 4.0 6.0
Communication mm2 VCTF 0.75~1.5(2P) VCTF 0.75~1.5(2P)
Set
Dimension
Net Weight
DVM S HP
kg
235.0 278.0
DVM S HR 214.0 184.0
Shipping
Weight
DVM S HP
kg
254.0 297.0
DVM S HR 260.0 303.0
Net Dimension(WxHxD) mm 1295x1695x765 1295x1695x765
Gross Dimension(WxHxD) mm 1363x1857x832 1363x1857x832
Operating
Temp
Range
Cooling
DVM S HP
-5.0~48.0 -5.0~48.0
DVM S HR -15.0~48.0 -15.0~48.0
Heating -20.0~24.0 -20.0~24.0
Outdoor Unit (cont.)
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.