Loading...
Product Specications
Samsung Electronics 2-17
Outdoor Unit (cont.)
TYPE
DVM S
Model AM180FXVAGH AM200FXVAGH AM220FXVAGH
Mode HP HP HP
Power Ø,V,Hz 3/AC380~415/50 3/AC380~415/50 3/AC380~415/50
Capacity
Horse Power HP 18 20 22
Cooling
kW 50.4 56.0 61.6
btu/h 171,900 191,000 210,000
Heating
kW 56.7 63.0 69.3
btu/h 193,500 215,000 236,000
Power
Power Input
(Nominal)
Cooling 1)
kW
12.80 15.19 17.35
Heating 2) 11.90 13.90 16.70
Current Input
(Nominal)
Cooling 1)
A
20.70 24.40 27.80
Heating 2) 19.10 22.30 26.80
Running
Current
Cooling A 20.70 24.40 27.80
Heating A 19.10 22.30 26.80
Max. A 39.10 42.50 44.50
Power
Consumption
Cooling kW 12.88 15.19 17.35
Heating kW 11.90 13.90 16.70
MCA / MFA A 48.9 / 50 52.5 / 75 52.5 / 75
COP
Nominal Cooling - 3.91 3.69 3.55
Nominal Heating - 4.76 4.53 4.15
ESEER (HP) 6.59 6.56 6.25
Compres-
sor
Model - DS-GB066FA**** DS-GB066FA**** DS-GB066FA****
Type INV x2 INV x2 INV x2
Output kW 5.8 x2 5.8 x2 5.8 x2
Lubricant
Type - FVC68D FVC68D
Charging cc 6,200
6,200 6,200
Refriger-
ant
Type - R410A R410A R410A
Factory Charging kg 8.7 8.4 8.4
FAN
Type - Propeller + BLDC Propeller + BLDC Propeller + BLDC
Motor Output W 630 x2 630 x2 630 x2
Airflow rate
/min
270 275 280
Pipe
Piping
Connections
Liquid
Ø,mm 15.88 15.88 15.88
Ø,inch 5/8" 5/8" 5/8"
Gas
Ø,mm 28.58 28.58 28.58
Ø,inch 1 1/8" 1 1/8" 1 1/8"
Dis. Gas
Ø,mm 22.22 28.58 28.58
Ø,inch 7/8" 1 1/8" 1 1/8"
Installation
Limitation
Max.Length m 200(220) 200(220) 200(220)
Max.Height m 110(40) 110(40) 110(40)
Cable
Main Power(Below/about20m) mm2 10.0 10.0 10.0
Communication mm2 VCTF 0.75~1.5(2P) VCTF 0.75~1.5(2P) VCTF 0.75~1.5(2P)
Set
Dimen-
sion
Net Weight
DVM S HP
kg
300.0 300.0 300.0
DVM S HR 306.0 306.0 306.0
Shipping Weight
DVM S HP
kg
319.0 319.0 319.0
DVM S HR 325.0 325.0 325.0
Net Dimension(WxHxD) mm 1295x1695x765 1295x1695x765 1295x1695x765
Gross Dimension(WxHxD) mm 1363x1857x832 1363x1857x832 1363x1857x832
Operating
Temp
Range
Cooling
DVM S HP
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
DVM S HR -15.0~48.0 -15.0~48.0
-15.0~48.0
Heating -20.0 ~ 24.0 -20.0 ~ 24.0 -20.0 ~ 24.0
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.

Table of Contents