Key Options
Samsung Electronics 8-3
How to set the key function of the outdoor unit (cont.)
■ AM080BXM*GH/EU
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency operation
for compressor
malfunction
Main 0 0
0 0 Disabled (Factory Default)
0 1 Not applicable
0 2 Not applicable
Cooling capacity
correction
Main 0 1
0 0 7-9 (Factory default)
Targeted evaporation temperature [
°C].
(When low temperature value is set, discharged
air temperature of the indoor unit will decrease)
0 1 5-7
0 2 9-11
0 3 10-12
0 4 11-13
0 5 12
-14
0 6 13-15
Capcity correction for
heating
Main 0 2
0 0 3.0 (Factory default)
Targeted high pressure [MPa].
(When low pressure value is set, discharged air
temperature of the indoor unit will decrease)
0 1 2.5
0 2 2.6
0 3 2.7
0 4 2.8
0 5 2.9
0 6 3.1
0 7 3.2
0 8 3.3
Current restriction rate Main 0 3
0 0 100% (Factory default)
When restriction option is set, cooling and
heating performance may decrease.
0 1 95 %
0 2 90 %
0 3 85 %
0 4 80 %
0 5 75 %
0 6 70 %
0
7 65 %
0 8 60 %
0 9 55 %
1 0 50 %
1 1 No restriction
Oil collection interval Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Temperature to trigger
defrost operation
Main 0 5
0 0 Factory default
0 1
Apply setting when the product is
being installed in humid area such as
near river or lake
Fan speed correction
for outdoor unit
Main 0 6
0 0 Factory default
0 1 Increase fan speed
Increase the outdoor unit's fan speed to
maximum va
lue
Silent mode for night-
time
Main 0 7
0 0 Disabled (Factory default)
0 1 LEVEL 1
Enable silent mode for night-time0 2 LEVEL 2
0 3 LEVEL 3
High-head condition
setting
Main 0 8
0 0 Disabled (Factory default)
0 1 Not applicable
0 2 Not applicable
0 3 Not applicable