Key Options
8-4 Samsung Electronics
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Long-pipng condition setting
(Setting is unnecessary if high-
head condition is set)
Main 0 9
0 0 Disabled (Factory Default)
0 1 LEVEL 1
When equivalent length of farthest indoor unit from the
outdoor unit is over 100m
0 2 Not applicable
Energy saving setting Main 1 0
0 0 Disabled (Factory default)
0 1 Enabled
Energy saving mode triggers when the room
temp
erature reaches desired temperature while
operating in heating mode.
Not applicable Main 1 1
0 0 Not applicable
0 1 Not applicable
Not applicable Main 1 2
0 0 Not applicable
0 1 Not applicable
Channel address Main 1 3
A U
Automatic setting
(factory default)
Address for classifying the product from upper level
controller(DMS,S-NET 3,etc.)
0 - 15
Manual setting for channel
0 – 15
Snow accumulation
prevention control
Main 1 4
0 0 Enable
d
During snow accmulation , the fan may spin even when
the unit is not in operation
0 1 Disabled (Factory default)
How to set the key function of the outdoor unit (cont.)