8-6 Samsung Electronics
[Caution]
• Edited option will not be saved if you do not end the option setting as explained in above instruction.
While you are setting the option, you may press and hold the K1 button to reset the value to previous setting.
If you want to restore the setting to factory default, press and hold the K4 button while you are in the option setting mode.
- If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored setting is saved. Press and hold the K2
button. When the segments shows that tracking mode is in progress, setting will be saved.
Optional item
Input
unit
SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency operation
for compressor
malfunction
Main 0 0
0 0 Disabled (Factory Default)
0 1 Not applicable
0 2 Not applicable
Cooling capacity
correction
Main 0 1
0 0 7-9 (Factory default)
Targeted evaporation
temperature [°C].
(When low temperature value is set,
discharged air temperature of the
indoor unit will decrease)
0 1 5-7
0 2 9-11
0 3 10-12
0 4 11-13
0 5 12-14
0 6 13-15
Capcity correction for
heating
Main 0 2
0 0 3.0 (Factory default)
Targeted high pressure [MPa].
(When low pressure value is set,
discharged air temperature of the
indoor unit will decrease)
0 1 2.5
0 2 2.6
0 3 2.7
0 4 2.8
0 5 2.9
0 6 3.1
0 7 3.2
0 8 3.3
Current restriction rate Main 0 3
0 0 100% (Factory default)
When restriction option is set,
cooling and heating performance may
decrease.
0 1 95 %
0 2 90 %
0 3 85 %
0 4 80 %
0 5 75 %
0 6 70 %
0 7 65 %
0 8 60 %
0 9 55 %
1 0 50 %
1 1 No restriction
Oil collection interval Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Temperature to trigger
defrost operation
Main 0 5
0 0 Factory default
0 1
Apply setting when the
product is being installed
in humid area such as near
river or lake
Fan speed correction
for outdoor unit
Main 0 6
0 0 Factory default
0 1 Increase fan speed
Increase the outdoor unit's fan speed to
maximum value
Silent mode for
night-time
Main 0 7
0 0 Disabled (Factory default)
0 1 LEVEL 1
Enable silent mode for night- time0 2 LEVEL 2
0 3 LEVEL 3
How to check the view mode using a tact switch (cont.)