EasyManua.ls Logo

Samsung AM080BXMDGH/EU - Page 122

Samsung AM080BXMDGH/EU
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Samsung Electronics 8-7
Optional item
Input
unit
SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
High-head condition
setting
Main 0 8
0 0 Disabled (Factory default)
0 1 Not applicable
0 2 Not applicable
0 3 Not applicable
Long-pipng condition
setting
(Setting is unnecessary
if high-head condition is
set)
Main 0 9
0 0 Disabled (Factory Default)
0 1 LEVEL 1
When equivalent length of farthest
indoor unit from the outdoor unit is
over 100m
0 2 Not applicable
Energy saving setting Main 1 0
0 0 Disabled (Factory default)
0 1 Enabled
Energy saving mode triggers when
the room temperature reaches desired
temperature while operating in
heating mode.
Not applicable Main 1 1
0 0 Not applicable
0 1 Not applicable
Not applicable Main 1 2
0 0 Not applicable
0 1 Not applicable
Channel address Main 1 3
A U
Automatic setting (factory
default)
Address for classifying the product
from upper level controller
(DMS,S-NET 3,etc.)
0 - 15
Manual setting for channel
0 – 15
Snow accumulation
prevention control
Main 1 4
0 0 Enabled During snow accmulation , the fan
may spin even when the unit is not in
operation
0 1 Disabled (Factory default)
Silent mode for external
contact
Main 1 5
0 0 -
If the external contact interface
module (MIM-B14) is used, entering the
silent mode is available with contact
signal.
0 1 LEVEL 1
0 2 LEVEL 2
0 3 LEVEL 3
How to check the view mode using a tact switch (cont.)