EasyManua.ls Logo

Samwon Tech TEMI880 - Page 104

Default Icon
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SAMWONTECH
4th Edition of TEMI880 IM : Jan. 29. 2007 Page 102 / 119
Share running D-Register
D-Reg. Symbol Description
D0001 TEMP_NPV Present Temp. PV
D0002 TEMP_NSP Present Temp. SP
D0003 WET_NPV Present wet part Temp. PV
D0004 WET_NSP Present wet part Temp. SP
D0005 HUMI_NPV Present Humi. PV
D0006 HUMI_NSP Present Humi. SP
D0007 TEMP_MVOUT Output of Temp.
D0008 HUMI_MVOUT Output of Humi.
D0009 C_PIDNO Number of running P.I.D
FIX running D-Register
D-Reg. Symbol Description
D0020 PROC_TIME_H FIX running PROCESS TIME (hour)
D0021 PROC_TIME_M FIX running PROCESS TIME (min)
PROGRAM running D-Register
D-Reg. Symbol Description
D0025 RUN_PTNO Number of running program pattern
D0026 RUN_SEGNO Number of running segment
D0027 REMAIN_TIME_H Remaining time(hour) of running segment
D0028 REMAIN_TIME_M Remaining time(min) of running segment
D0029 WAIT_TIME_H WAIT TIME(hour) of waiting
D0030 WAIT_TIME_M WAIT TIME(min) of waiting
D0031 NOW_PT_RPT Repeat times of present running pattern
D0032 TOTAL_PT_RPT Repeat times of setting pattern
D0033 NOW_SEG_RPT Repeat times of present running segment
D0034 TOTAL_SEG_RPT Repeat times of setting segment
D0035 PREV_TEMP_TSP Previous segment Temp. TSP(Target Set Point)
D0036 NOW_TEMP_TSP Present segment Temp. TSP(Target Set Point)
D0037 PREV_HUMI_TSP Previous segment Humi. TSP(Target Set Point)
D0038 NOW_HUMI_TSP Present segment Humi. TSP(Target Set Point)
D0039 NOW_SEG_TIME Setting time of present segment

Related product manuals