4.4.2 FUNCTION
Function group is consisted of D-Registers for operation
PROGRAM running D-Register
D-Reg. Symbol Description
D0100 SET_PTNO Set pattern number
D0121 WAITMD Select using WAIT function ( 0 : OFF 1 : ON )
D0122 TEMP_WATE_ZONE Set wait zone of Temp.
D0123 HUMI_WATE_ZONE Set wait zone of Humi.
D0124 WAIT_TIME Set wait time
FIX running D-Register
D-Reg. Symbol Description
D0102 FIX_TEMP_SP Set Temp. SP on FIX running
D0103 FIX_HUMI_SP Set Humi. SP on FIX running
D0110 FIX_OPTM_SELL Select using FIX OP TIME ( 0 : OFF 1 : ON )
D0111 FIX_OPTM_H Set the hour for FIX OP TIME
D0112 FIX_OPTM _M Set the minute for FIX OP TIME
Operation D-Register
D-Reg. Symbol Status Value Description
RUN 1 PROG/FIX RUN
HOLD 2 HOLD ON/OFF
STEP 3 SEGMENT STEP
D0101 STATUS_MODE
STOP 4 PROG/FIX STOP
PROG 0 SET PROG MODE
D0104 OP_MODE
FIX 1 SET FIX MODE
STOP 0 SET STOP MODE
COLD 1 SET COLD MODE
D0105 PWR_MODE
HOT 2 SET HOT MODE
For PROG RUN(or FIX RUN) through communication, TEMI880 must be STOP(PROG STOP/FIX STOP).
Ex) TEMI880 should be PROG STOP(D0104 = 0001, D0101 = 0004) for switching FIX RUN to PROG RUN.