22 S&C Instruction Sheet 695-535
Programming the Control Settings
The Control Settings selection tab is where the user and admin passwords are changed,
where the Interrupter ID can be modied, where the global settings can be modied,
and where the control can be reset back to factory defaults. This is also where the USB
Network settings can be viewed. USB Network settings are not editable.
With the exception of changing the user password, only the admin login can make
changes to the Control Settings menu.
Some of the Control Settings are programmed by S&C at the factory. The interrupter
IDs are programmed to match the “way” designation of the Vista SD switchgear. S&C
will also program the following global settings: Continuous Current Rating, Fault
Interrupting Rating, and Trip Mode.
Before energizing the Vista SD switchgear, you must:
Change the User and Admin passwords from their factory default settings.
Conrm the 60-Hz system frequency is the default setting.
Confirm the continuous current rating matches the ratings of the Vista SD
switchgear as listed on the nameplate.
Conrm the fault-interrupting rating matches the rating of the Vista SD switchgear
as listed on the nameplate.
Check that the Trip Mode setting matches the capabilities of the switchgear and
the application. Vista SD Underground Distribution Switchgear is a three-phase trip
device and should only be set to three-phase trip/three-phase lockout. Three-phase
trip/three-phase lockout fault interrupters cannot be set to the Single-Phase Trip
setting or the switchgear may not respond properly to faults.
NOTICE
The overcurrent control will logout the user after five minutes of inactivity. Any
settings not saved before the inactivity logout will be lost.
To change the admin or user password:
STEP 1. Click on the Control Settings tab in the Selection menu. Scroll down to the
Change Admin or Change User Password tab. Enter the present password.
When changing the admin password for the rst time, enter the default
password noted in the “Logging In for the First Time” section on page 15. See
Figure 15.
STEP 2. Enter a new password, an alpha-numeric sequence of a minimum of four
characters and a maximum of 12 characters with at least one letter, one
number, and one special character: !, #, $, *, _ or – into the New Password eld.
Passwords are case sensitive. Re-enter the new password in the Conrm
Password eld.
STEP 3. Click on the Save button directly under the change password section.
A message that the password has been saved successfully will display.
Figure 15. The Change Admin Password menu.
Changing the Admin
and User Password