Programming the Control Settings
At the factory, S&C Electric Company renames the fault interrupter to match its way
designation depending on the switchgear conguration. (i.e. if the fault interrupter is
on Way 4, the fault interrupter will be named “Way 4.”)
The fault interrupter IDs can be changed to match the application.
To change the names:
STEP 1. Select the appropriate interrupter eld and type in the desired name. See
Figure 16. Interrupter names can be up to 16 characters excluding special
characters such as “/, &, #, $, and :”. This name will be propagated throughout
the Overcurrent Control settings and will change the name in the Selection
menu, Event logs, Trip test screen, and Status screen.
Figure 16. The Change Interrupter ID menu.
STEP 2. Click on the Save button. A message that the setting has been saved will
display.
The Global Settings are programmed at the factory to match the Vista SD switchgear
model. Recheck all settings to make sure they are accurate before energizing the
switchgear. If the switchgear is applied at 50 Hz, select 50 Hz under the Global Settings
menu.
NOTICE
If problems are encountered trying to change the Global Settings while running
Microsoft Internet Explorer in Compatibility mode, disable Compatibility mode or
try again using a different Web browser.
NOTICE
The overcurrent control will logout the user after five minutes of inactivity. Any
settings not saved before the inactivity logout will be lost.
Changing the
Interrupter ID
Changing the Global