24 S&C Instruction Sheet 695-535
Programming the Control Settings
Nominal Frequency
The Nominal Frequency setting congures the overcurrent control for the operating
frequency of the switchgear. To change the switchgear frequency:
STEP 1. From the Global Settings menu, select the frequency setting to match the
system operating frequency. See Figure 17.
Figure 17. Select the nominal frequency from the Global Settings menu.
STEP 2. Click on the Save button. A message will display showing that the setting has
been saved.
Continuous Current
The Continuous Current setting congures the overcurrent control for the turns ratio
of the switchgear’s current transformers. The turns ratio depends on the continuous
current rating of the switchgear:
Continuous Current, A Turns Ratio
600 660:1
Vista SD Underground Distribution Switchgear is only available in the 600-ampere
continuous current rating. To change the Continuous Current setting:
STEP 3. From the Global Settings menu, select the 600-A (660:1 CT Ratio) continuous
current rating. See Figure 18.
STEP 4.
Figure 18. Select the continuous current from the Global Settings menu.
Click on the Save button. A message will display showing that the setting has
been saved.