S&C Instruction Sheet 695-535 19
Understanding the Status Display
The Status screen and menus provide a summary of the status of the overcurrent control,
measurement of the load current of the associated fault interrupters, and the control
settings. It also provides a summary of the login status, the overcurrent control serial
number and MAC address, and the rmware installed on the control. This page can be
viewed from admin and user logins and when using the View button.
The overcurrent control has a physical LED status display located on the outside of
the electronics module that is visible when the overcurrent control is removed from its
enclosure. An on-screen replica of this status display can be viewed when a computer is
connected to the control. See Figure 14. See Table 2 for the LED key.
Figure 14. The Status screen.
Table 2. Status Display LED Key
LED Key Description
Orange Trip operation recorded
Red Element initiated trip
Green
Flashing: Control OK
Solid: Control Error
White All prior trip operations cleared