30 S&C Instruction Sheet 695-535
STEP 3.
After entering the Overcurrent Protection settings, click on the Save button.
A conrmation message will be displayed. See Figure 23.
Figure 23. A Time Overcurrent Phase Protection confirmation message.
If the coordination settings selections are invalid, or contradictory, an error
message explaining the problem will appear, and any cell with an invalid value
will be highlighted in yellow after clicking on the Save button. Please note that
selections will not be saved until the error is fixed. See Figure 24.
Figure 24. A Time Overcurrent Phase Protection Error message.
STEP 4. When programming the overcurrent control is completed, make sure to replace
the data port cover and ensure it is secure. S&C recommends re-checking the
control settings on the Status screen before leaving the overcurrent control.
NOTICE
Make sure the data port cover is secure after programming the control. Failure to
secure the data port cap may result in damage to the data port. A control with a
damaged data port cannot be accessed via personal computer.
Overcurrent Protection Setting Denitions