38 S&C Instruction Sheet 695-535
Factory Defaults and Factory Default Reset
A confirmation window will open asking to confirm resetting of the over-
current control. Click on the OK button to reset the overcurrent control. See
Figure 26.
Figure 26. Click on the OK button to confirm resetting the overcurrent control to the factory-default.
STEP 3. When the factory reset is complete, a conrmation message will appear. See
Figure 27.
Figure 27. The factory reset confirmation message.
After Resetting Factory Default Settings
The following steps must be completed after resetting the factory default settings:
STEP 1. Change the overcurrent control passwords as explained in the “Logging in for
the First Time” section on page 15.
STEP 2. Make sure the Global Settings (Frequency, Continuous Current, Fault
Interrupting Rating, and Trip Mode) match the conguration of the system
and the Vista Underground Distribution Switchgear as stated on the switchgear
nameplate as explained in the “Changing the Global Settings” section on
page 23. Take particular note of the fault-interrupting rating and the trip mode.
Vista SD Underground Distribution Switchgear comes in 16-kA and 12.5-kA
interrupting ratings, and ONLY comes in the Three-Phase Trip/Three Phase
Lockout trip mode.
STEP 3. Update the Interrupter IDs to match the way designations on the Vista SD
switchgear, or change to the user's preferred naming convention.
STEP 4. Reprogram the Overcurrent Protection Settings as explained in the
“Programming the Overcurrent Protection Settings” section on page 28.