Group/
Item
Item Name Function Initial Range Note
34 FAN_2_TEMPERROR_SPEED FAN1 Voltage at Temp. Failure 130 / 130 0-255
35 Cooling Time L1
Cooling Time Setting for Fan Mode L1
(x30sec) 1: 30 sec, 3: 90 sec, 15: 450 sec.
3 / 3
1-15
36 Cooling Time L2
Cooling Time Setting for Fan Mode L2
(x30sec) 1: 30 sec, 3: 90 sec, 15: 450 sec.
4 / 4
1-15
37 IGNORE_TEMP_CHANGE_RATE
Decides Ignore Temp. Failure at the Temp.
rising (X/10) ºC a second
(0.1ºC step, Initial Value 10=1ºC)
10 / 10
5-50
38
I G N O R E _ T E M P _ C H A N G E _
TIMES
Decides Temp Failure when ingore temp
occurs X times
5 / 5
1-9
42 NOR_TEMP_FAN1_MIN FAN1 Control Start Tempurature in Normal 31 / 30 0-255
43 NOR_TEMP_FAN1_MAX FAN1 Control End Tempurature in Normal 36 / 40 0-255
44 NOR_TEMP_FAN2_MIN FAN2 Control Start Temprature in Normal 31 / 30 0-255
45 NOR_TEMP_FAN2_MAX FAN2 Control End Tempurature in Normal 37 / 41 0-255
46 NOR_VALU_FAN1_MIN
FAN1 Control Mini Value in Normal
(0:Fan Voltage
0V,255: Fan Voltage 25.5V)
65 / 53
0-255
47 NOR_VALU_FAN1_MAX FAN1 Control Max Value in Normal 135 / 130 0-255
48 NOR_VALU_FAN2_MIN FAN2 Control Mini Value In Normal 75 / 75 0-255
49 NOR_VALU_FAN2_MAX FAN2 Control Max Value In Normal 130 / 130 0-255
50 ECO_TEMP_FAN1_MIN FAN1 Control Start Tempurature in Eco 31 / 28 0-255
51 ECO_TEMP_FAN1_MAX FAN1 Control End Tempurature in Eco 36 / 39 0-255
52 ECOTEMP_FAN2_MIN FAN2 Control Start Temprature in Eco 31 / 28 0-255
53 ECO_TEMP_FAN2_MAX FAN2 Control End Tempurature in Eco 37 / 40 0-255
54 ECO_VALU_FAN1_MIN FAN1 Control Mini Value in Eco 55 / 38 0-255
55 ECO_VALU_FAN1_MAX FAN1 Control Max Value in Eco 125 / 120 0-255
56 ECO_VALU_FAN2_MIN FAN2 Control Mini Value In Eco 55 / 55 0-255
57 ECO_VALU_FAN2_MAX FAN2 Control Max Value In Eco 115 / 115 0-255
58 HINOR_TEMP_FAN1_MIN
FAN1 Control Start Temperature in High-land
Normal
29 / 29
0-255
59 HINOR_TEMP_FAN1_MAX
FAN1 Control End Temperature in High-land
Normal
29 / 29
0-255
60 HINOR_TEMP_FAN2_MIN
FAN2 Control Start Temperature in High-land
Normal
29 / 29
0-255
61 HINOR_TEMP_FAN2_MAX
FAN2 Control End Temperature in High-land
Normal
29 / 29
0-255
62 HINOR_VALU_FAN1_MIN FAN1 Control Min Value in High-land Normal 135 / 131 0-255
63 HINOR_VALU_FAN1_MAX FAN1 Control MaxValue in High-land Normal 135 / 131 0-255
64 HINOR_VALU_FAN2_MIN FAN2 Control Min Value in High-land Normal 130 / 130 0-255
65 HINOR_VALU_FAN2_MAX FAN2 Control MaxValue in High-land Normal 130 / 130 0-255
66 HIECO_TEMP_FAN1_MIN
FAN1 Control Start Temperature in High-land
Eco
30 / 30
0-255
67 HIECO_TEMP_FAN1_MAX
FAN1 Control End Temperature in High-land
Eco
30 / 30
0-255
68 HIECOTEMP_FAN2_MIN
FAN2 Control Start Temperature in High-land
Eco
30 / 30
0-255
69 HIECO_TEMP_FAN2_MAX
FAN2 Control End Temperature in High-land
Eco
30 / 30
0-255
70 HIECO_VALU_FAN1_MIN
FAN1 Control Min Value in High-land
Eco
125 / 125
0-255
71 HIECO_VALU_FAN1_MAX
FAN1 Control MaxValue in High-land
Eco
125 / 125
0-255
72 HIECO_VALU_FAN2_MIN
FAN2 Control Min Value in High-land
Eco
115 / 115
0-255
73 HIECO_VALU_FAN2_MAX
FAN2 Control MaxValue in High-land
Eco
115 / 115
0-255
74 CLNOR_TEMP_FAN1_MIN
FAN1 Control Start Temperature in Ceiling
Normal
29 / 28
0-255
75 ClNOR_TEMP_FAN1_MAX
FAN1 Control End Temperature in Ceiling
Normal
36 / 41
0-255
76 CLNOR_TEMP_FAN2_MIN
FAN2 Control Start Temperature in Ceiling
Normal
29 / 28
0-255
77 CLNOR_TEMP_FAN2_MAX
FAN2 Control End Temperature in Ceiling
Normal
37 / 42
0-255
78 CLNOR_VALU_FAN1_MIN FAN1 Control Min Value in Ceiling Normal 70 / 68 0-255
79 CLNOR_VALU_FAN1_MAX FAN1 Control MaxValue in Ceiling Normal 135 / 131 0-255
80 CLNOR_VALU_FAN2_MIN FAN2 Control Min Value in Ceiling Normal 80 / 80 0-255
81 CLNOR_VALU_FAN2_MAX FAN2 Control MaxValue in Ceiling Normal 130 / 130 0-255
82 CLECO_TEMP_FAN1_MIN
FAN1 Control Start Temperature in Ceiling
Eco
30 / 29
0-255
83 CLECO_TEMP_FAN1_MAX
FAN1 Control End Temperature in Ceiling
Eco
36 / 40
0-255
84 CLECOTEMP_FAN2_MIN
FAN2 Control Start Temperature in Ceiling
Eco
30 / 29
0-255
85 CLECO_TEMP_FAN2_MAX
FAN2 Control End Temperature in Ceiling
Eco
37 / 41
0-255
86 CLECO_VALU_FAN1_MIN FAN1 Control Min Value in Ceiling Eco 60 / 55 0-255
87 CLECO_VALU_FAN1_MAX FAN1 Control MaxValue in Ceiling Eco 125 / 122 0-255
88 CLECO_VALU_FAN2_MIN FAN2 Control Min Value in Ceiling Eco 60 / 60 0-255
89 CLECO_VALU_FAN2_MAX FAN2 Control MaxValue in Ceiling Eco 115 / 115 0-255
90 FAN_1_AUTO_ADJ 0: OFF (Manual), 1: ON (Auto) - 0-1