Design of Mini ECO-i SYSTEM
1. Model Selecting and Capacity Calculator
I Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (2))
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
SPW-CR485GX(H)56
130
120
110
100
90
80
70
60
50
40
15
20
25
( C DB)
SPW-CR365GX(H)56
( C DB)
130
120
110
100
90
80
70
60
50
40
15
20
25
SPW-CR605GX(H)56
130
120
110
100
90
80
70
60
50
40
15
20
25
( C DB)
Outdoor unit heating capacity characteristics
Outdoor air intake temp. ( C DB)
20 –15 –10 –5 0 5 10 15
Outdoor air intake temp. ( C DB)
20 –15 –10 –5 0 5 10 15
Outdoor air intake temp. ( C DB)
–20 –15 –10 –5 0 5 10 15
Outdoor intake air
–20–15–10–8–6–5–4–2–10123456
temp. (°C WB RH 85%)
Correction
0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
coefficient
Capacity ratio (%)
Capacity ratio (%)
Capacity ratio (%)