3
3 - 51
Control of Mini ECO-i SYSTEM
4. System Controller
SW1
1
ON
ALL mode
ZONE 1 mode
ZONE 2 mode
ZONE 3 mode
ZONE 4 mode
OFF
OFF
ON
OFF
ON
2
OFF
OFF
OFF
ON
ON
3
OFF
4
OFF
ON
ON
ON
ON
5
OFF
2 3 4
SW1
5 6 7 8
Main/sub selection switch
OFF: System controller operates as main controller.
ON: System controller operates as sub-controller.
ALL/ZONE mode selection switch
ALL mode:
All indoor units can be controlled by system controller ZONE
1, 2, 3, 4 mode:
Indoor units in one of zone 1, 2, 3, or 4 can be controlled by
system controller. All indoor units cannot be set.
Central control/Remote control mode selection switch.
OFF: Central control mode
Individual setting by remote controller can be inhibited by
system controller.
ON: Remote control mode
Setting by system controller is inhibited by other central
control equipments.
Central control Main/Sub selection switch
(OFF: Main, ON: Sub)
When AMY adaptor etc. is used with system controller,
set the switch to ON position.
When only 1 system controller is used, set the switch
to OFF position.
Except , when multiple system controllers are used, set
only 1 system controller to OFF position others to ON
position.
ALL mode system controller to be OFF position.
(recommended)
1
2
3 1
(Central control) button operation switch
OFF: (Central control) button operation is permitted.
ON : button operation is inhibited.
*All switches are in OFF position at shipment.