Design of Mini ECO-i SYSTEM
3. Installation Instructions
3-1. Indoor Unit
AVOID:
G areas where leakage of flammable gas may be
expected.
G places where large amounts of oil mist exist.
G direct sunlight.
G locations near heat sources which may affect the
performance of the unit.
G locations where external air may enter the room
directly. This may cause “sweating” on the air
discharge ports, causing them to spray or drip.
G locations where the remote controller will be
splashed with water or affected by dampness or
humidity.
G installing the remote controller behind curtains or
furniture.
G locations where high-frequency emissions are
generated.
DO:
G select an appropriate position from which every
corner of the room can be uniformly cooled.
G select a location where the ceiling is strong enough
to support the weight of the unit.
G select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
G allow room for operation and maintenance as well
as unrestricted air flow around the unit.
G install the unit within the maximum elevation
difference above or below the outdoor unit and
within a total tubing length (L) from the outdoor unit
as detailed in Table 2-10.
G allow room for mounting the remote controller about
1 m off the floor, in an area that is not in direct
sunlight nor in the flow of cool air from the indoor
unit.
Air delivery will be degraded if the distance from the
floor to the ceiling is greater than 3 m (for LD type,
greater than 3.5 m).
NOTE
Concealed-Duct Type
4-Way Semi-Concealed T
ype
1 m
1 m
1 m
1 m
1 m
2-Way,
Wall-Mounted Type
min.15 cm
Front View
min.
15 cm
min.
15 cm
Floor-Standing, Concealed Floor-Standing Type
min.
10 cm
min. 100 cm
min.
10 cm
min. 100 cm
Horizontal view Vertical view
Ceiling-Mounted Type
Side view
min. 25 cm
The rear of the indoor unit can be installed flush
against the wall.
min. 50 cm
Air intake
Air
discharge
min. 25 cm
Ceiling
Wall
Front view
Max. 25 cm
Obstacle
NOTE
Fig. 2-1
Fig. 2-2
20 cm
20 cm
100 cm
20 cm
100 cm
min. 5 cm
min. 5 cm
min. 1 m
Air
intake
Air
discharge
Obstacle
Ceiling
Wall
Wall
Side view
Semi-Concealed Type Semi-Concealed Slim Type
1-Way Semi-Concealed & Slim Type
Fig. 2-3
Fig. 2-5
Fig. 2-4
06-405 Mini-ECOi_TD2 11/6/06 5:14 PM Page 25