3
3 - 20
Control of Mini ECO-i SYSTEM
2. Wireless Remote Controller
2-19. Important Information for Installation of
1 Separate Receiver Unit
<Installation location>
G Do not install in a location where the air contains oil
mist, such as in a kitchen or factory.
G Do not install next to a window, or in any other
location directly exposed to sunlight and outside
air.
G Do not install nearby devices which can be expect-
ed to produce electrical noise, such as elevators,
automatic doors, and industrial sewing machines.
G If the receiver unit is installed near a rapid-start
type or inverter-type fluorescent lamp (a lamp
which does not include a glow lamp), it may not be
possible to receive the wireless remote controller
signal in some cases. In order to prevent interfer-
ence from fluorescent lamps, leave a minimum of
2 meters between the receiver unit and the fluores-
cent lamps, and install the receiver unit in a loca-
tion where it can receive the wireless remote con-
troller signal when the fluorescent lamps are lit.
2-20. How to Install the Separate Receiver Unit
G To avoid malfunction of the remote controller, do
not assemble or run remote control wiring together
with the power cables, and do not enclose them in
the same metal conduit.
G When the power unit induces electrical noise, it is
recommended that a noise filter or the like be
installed.
No. Parts
No.