Mini ECO-i SYSTEM Unit Specifications
10. Concealed Floor-Standing Type (FM Type)
Unit specifications (D)
MODEL No. Indoor Unit SPW-FMR164GXH56(A/B)
POWER SOURCE 220 - 230 - 240 V / Single-phase / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW
5.6 6.3
BTU / h 19,000 21,000
Air circulation (Hi / Me / Lo) m
3
/h 900 / 780 / 660
Moisture removal (High) Liters/h
2.5
ELECTRICAL RATINGS
Voltage rating 240 220 230
240
Available voltage range
198 – 264 198 – 264
Running amperes A
V
V
0.54 0.56 0.58 0.37
0.41 0.43
Power input W 116 126 136 79 91
101
Power factor % 98 98 98 97 97 98
Max. starting amperes
A
11 1 11 1
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air filter Washable, easy access
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 39 / 36 / 31
Refrigerant tubing connections Flare type
Refrigerant tube diameter Liquid tube mm (in.) 6.35 (1/4)
Gas tube mm (in.)
12.7 (1/2)
Drain connection 20A, OD26 mm
Remote controller
Optional (RCS-SH80AG)
Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) Munsell 10Y 9.3 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT Package dimensionsUnit dimensions
Unit dimensions
Height mm (in.)
616 (24-8/32) 679 (26-23/32)
1291 (50-26/32)
312 (12-9/32)
0.273 (9.6)
Width mm (in.)
1219 (48)
Depth mm (in.)
229 (9-1/32)
Net weight kg (lbs.)
Shipping weight kg (lbs.)
Shipping volume m
3
(cu. ft)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
220
230
28 (62)
31 (68)