3
3 - 17
Control of Mini ECO-i SYSTEM
2. Wireless Remote Controller
2-14. Accessories
2-15. Wiring the Receiver Unit
G Connection diagram
1. Connect W1 to the indoor unit remote controller
wiring terminal. (It has no polarity.)
2. Connect W3 from the display and W2 from the
control unit to the relay connector.
2-16. Precautions on Simultaneous Installation of
Wired Remote Controller and
Wireless Remote Controller
By installing a wired remote controller, the wireless
receiver unit can permit dual remote control
operation at the same time.
(Up to 2 units of remote controllers – a wireless
remote controller and a wired remote controller –
can be installed.)
Dual remote control operation can control 1 or
multiple air conditioners using several remote
controllers.
No.
1
2
3
4
5
Control unit
Display unit
Parts
Remote
control unit
Remote
control holder
AAA alkaline
battery
Spacer
Tapping screw
4 × 10 mm
Tapping screw
4 × 16 mm
Tr uss-head Phillips
Vinyl clamp
No.
Q’ty Parts Q’ty
6
7
8
9
2
1
1
1
1
2
4
2
3
L 150 mm
Control unit
CN1
6PWHT
6PWHT
2PWHT
WHT
BLK
W1 (1300mm)
1
2
W2 (200mm)
W3 (1200mm)
BLU
YEL
PNK
RED
GRY
BLK
BLU
YEL
PNK
RED
GRY
BLK
Remote
controller
terminal
board
Indoor unit
Display unit
Relay
connector
(6PWHT)
CN2
CN1
CAUTION
G Be sure to determine the correct
terminal numbers on the indoor
unit when wiring the remote con-
troller. The remote controller will
be damaged if high voltage (such
as 200 VAC) is applied.
06-405 Mini-ECOi_TD3 11/6/06 6:18 PM Page 17