4
4 - 131
Mini ECO-i SYSTEM Unit Specifications
8. Concealed Duct High Static Pressure Type (D Type)
Indoor unit (B)
MODEL No. SPW-DR364GXH56(A/B)
Power source
220 - 230 - 240 V / Single-phase / 50 Hz
Controller P.C.B. Ass’y
CR-TRP50A-B (Microprocessor)
Fan (Number…diameter) mm
Centrifugal (1 … ø 220)
Fan motor
Model…Nominal output W
KFC4X-201B5P … 200 W
Power source
220 - 230 - 240 V / Single-phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm 4P … 1,134
Coil resistance BRN WHT : 13.75 ORG YEL : 2.21
(Ambient temperature 20°C) WHT VLT : 4.47 YEL BLK
BLK PNK
:
:
10.33
12.90
VLT ORG :
1.20
Safety device
Operating temperature Open °C 130 ± 5
(115 ± 5)
Close
°C
Run capacitor VAC, µF 440 VAC, 5.0 µ
F
Electronic expansion valve
Coil UKV-U030E
Coil resistance (at 20°C) ORG GRY : 46 YEL GRY : 4
6
RED GRY : 46 BLK GRY : 4
6
Valve body
UKV-30D33
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows…fin pitch mm 4…2.0
Face area m
2
0.273