4
4 - 132
Mini ECO-i SYSTEM Unit Specifications
8. Concealed Duct High Static Pressure Type (D Type)
Indoor unit (C)
MODEL No. SPW-DR484GXH56(A/B)
Power source
220 - 230 - 240 V / Single-phase / 50 Hz
Controller P.C.B. Ass’y
CR-TRP50A-B (Microprocessor)
Fan (Number…diameter) mm
Centrifugal (1 … ø 250)
Fan motor
Model…Nominal output W
KFC4Q-401A5P … 400 W
Power source
220 - 230 - 240 V / Single-phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm 4P … 1,077
Coil resistance Ω BRN – WHT : 11.05 ORG – YEL : 4.57
(Ambient temperature 20°C) WHT – VLT : 1.80 YEL – PNK :
7.70
VLT – ORG :
1.00
Safety device
Operating temperature Open °C 130 ± 5
(115 ± 5)
Close
°C
Run capacitor VAC, µF 440 VAC, 7.0 µ
F
Electronic expansion valve
Coil UKV-U030E
Coil resistance (at 20°C) Ω ORG – GRY : 46 YEL – GRY : 46
RED – GRY : 46 BLK – GRY : 4
6
Valve body
UKV-30D33
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows…fin pitch mm 4…2.0
Face area m
2
0.273
06-405 Mini-ECOi_TD4 11/8/06 4:28 PM Page 132