7-3. Some part of air conditioner does not operate.
7-3-1. Only fan does not run.
7-3-2. Electric heater does not work.
Measure resistance of electric
heater winding.
Blown
Check continuity for thermal
fuse in heater assy.
Replace it.
Check PCB Ass'y. (Controller)
Check to see if thermal limit in
heater assy is opened or
closed.
Fan cannot
be turned.
OK
Check fan rotation.
Turn fan gently once or twice by
hand.
Check fan casing
foreign matter on
inside.
Fan motor burnout
or foreign matter in
bearings.
Remove foreign
matter or repair.
Repair or replace.
Measure resistance of fan motor
winding. (FMO or FMI)
Check fan motor capacitor.
(FMO or FMI).
Check PCB Ass'y . (Controller)
45