10-2. Freeze Prevention
This function prevents freezing of the indoor heat exchange coil.
When the temperature of the indoor heat exchange coil falls below 32°F, the compressor stops operation. The
compressor does not start again until the temperature rises above 50°F.
(*) Actual compressor OFF time indicated by "3 minutes" varies between 2 minutes 45 seconds to 4 minutes.
10-3. Freeze Protection
This function prevents the temperature within the room from dropping below freezing.
When the room temperature falls below 46.4°F, the electric heater comes ON to keep the room temperature
above freezing. This function always works at any operational mode even when the unit is OFF.
The following chart shows an example when the mode selector switch is at OFF position.
ON ON
OFF
High High
OFF
OFF
OFF
Room temp.
46.4 °F
47.3 °F
Heater
Indoor fan (*)
Room temp.
NOTE
(*) Indoor fan operation synchronizes with that of heater's thermo ON and OFF
regardless of fan cycle switch position.
ON ON
OFF
Set speed
Indoor heat exch.
coil temp.
32 °F
50 °F
Compressor
Indoor fan
(*) 3 minutes or more
Indoor heat exch. coil temp.
NOTE

Other manuals for Sanyo STW-2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sanyo STW-2 Series and is the answer not in the manual?

Sanyo STW-2 Series Specifications

General IconGeneral
BrandSanyo
ModelSTW-2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals