148
Using the Configurator
Options
Two stage Select this check box to configure the system as a two
stage system. If you do not select this, then the system is
single stage.
As per UL 864 and UL 2572 only a setting of Single Stage
(disabled) is permissible.
Fire drill Select this check box to enable the panel's Fire Drill
switch.
Manual signal silence Select this check box to enable the panel's Signal Silence
switch.
Style D (Class A) Conv
Inputs
Select this check box to indicate that the panel has Style
D (Class A) conventional inputs.
Style D (Class A) Input
Modules
Select this check box to indicate that input modules' field
wiring is Style D (Class A).
Style 6 and 7 (Class A) Loop Select this check box to indicate that the panel has Style 6
and 7 (Class A) addressable loops.
Style Z (Class A) Fire Phone Select this check box to indicate that the wiring from an
addressable fire phone module and the handset is Style Z
(Class A).
Style 7 (Class A) Network Select this check box to indicate that the wiring between
Network Nodes is Style 7 (Class A).
Digital Audio Select this check box to indicate that the audio signals
use the ARCNet wiring between network nodes. If this
option is not selected, then the audio runs over a separate
pair of wires.
Digital Phone Select this check box to indicate that the fire phones use
the ARCNet wiring between network nodes. If this option
is not selected, then the phones communicate over the
telephone bus terminals.
Suppress Manual Control
Trouble
Select this check box to suppress trouble for auto/man
switch on 24 switch adder (IPS-2424) and HOA (FDX-
008).
Monitor alert Select this check box to make an alert sound play when a
monitor input activates.
Second stage alarm relay Select this check box to set the alarm relay to operate on
a stage two alarm. This option is disabled unless Two
stage is selected. As per UL 864 and UL 2572 only a
setting of Disabled is permissible.
Relay follows node alarm Select this check box to set the alarm relay to activate on
a node level alarm. If this option is not selected, the alarm
relay activates on a system level alarm.
Relay follows node supv Select this check box to set the supervisory relay to
activate on node level supervisory. If it is not selected, the
supervisory relay activates on a system level supervisory.
Relay follows node trbl Select this check box to set the trouble relay to activate on
node level trouble. If it is not selected, the trouble relay
activates on system level trouble.

Table of Contents

Other manuals for Secutron MMX-2003-12NDS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MMX-2003-12NDS and is the answer not in the manual?

Secutron MMX-2003-12NDS Specifications

General IconGeneral
BrandSecutron
ModelMMX-2003-12NDS
CategoryControl Panel
LanguageEnglish

Related product manuals