165
Using the Configurator
To get the configuration information
• Click Get.
The Sent/received field will tell you if the configuration is out of date.
To automatically assign a UDACT group to every unassigned zone and output circuit
• Click Auto-Assign.
Account
Line
Attached Fire Alarm
Report Priority
Timers
Account ID Six digit decimal for the SIA report formats and four digit
hexadecimal for Contact ID.
Telephone The telephone number.
Report Choose SIA110, SIA300, or Contact ID.
Dial Using Select Tone or Pulse.
Wait for dial tone before
dialing
Select this check box if you want the dialer to wait for a
dial tone before dialing.
Communication Protocol Level 0, Level 1, Level 2 or Level 1G.
Checksum 8 Bit / 16 Bit.
Event Format Specifies whether the internal Ckt No or a combination of
Loop and Address is sent to the monitoring station.
Output Offset 0-9999. This value is added to outputs to differentiate
them from inputs with the same Ckt No.
Alarm Select the account that will report alarms.
Supervisory Select the account that will report supervisory alerts.
Trouble Select the account that will report trouble alerts.
AC loss delay If there is a loss of AC power, the dialer waits this amount
of time before calling the monitoring station.
Line 2 cellular test Select this check box to indicate that line 2 dials a cell
phone.
Select the day of the month for the cell phone test.
Auto test Select the time for a daily test of the lines.