50
LCD Programming
-- Delay: Sets the length of time the panel will wait before reporting the GRID package
off-line. This can be set from 10 to 255 seconds.
-- Disconnect: If enabled, the Common Disconnect hot key will shut down Port 3. The
GRID package will report the panel as offline.
Voice Evac.System
(MR2-8E Program): Allows for setting parameters related to the
connection to the MV2700 voice evacuation panel.
-- Mode: Selects how information is sent to the MV2700. There are the following
options:
DEVICE (default): Send the device address or internal circuit number without
translation.
ZONE: Send the LED number turned on for input circuits and devices and send the
internal circuit for internal circuits.
GROUP: Send the associated Group ID(s) for all conditions. Anything not
associated with a specific group sends a group number of 0.
-- Retry: Set the number of times to try to resend a message before giving up. If this
number of retries are attempted without success, the other panel is considered to
be off-line. The default value is 8. This would be increased only if the
communications line cycles between on-line and off-line. (Range: 1 to 25)
-- Disconnect: If enabled, the Common Disconnect hot key shuts down Port 3.
-- Baud: Set the communications baud rate. The available fixed baud rates are 9600,
4800, 2400, 1200, 600 and 300.
• Terminal: Select ANSI or TeleVideo protocol. Most terminals and terminal emulator
programs support ANSI protocol.
• Port 6: Allows for the setting of the baud rate to MR-2614 and MR-2644 annunciators,
the city tie modules, and the MRDL dialer. The settings are 4800 and 1200. If none of
these devices are programmed in the database, the message “nothing to program” is
shown.
3.3.9 Alarm List
This menu controls the operation of the Alarm List. This function is restricted to Privilege Level
2. It has the following options:
• Reset: Select when entries are taken out of the Alarm List. AUTO removes entries as
soon as the condition restores. MANUAL requires that Reset be pressed before they are
removed. Conditions that have restored are shown as a restored condition in the Alarm
List.
• Remote: Routes the messages for events from the panel to annunciators. The options
are:
-- ALL: All messages are sent to all annunciators.
-- SELECT: Messages are sent as directed in the database.
3.3.10 Passcode
Allows for the changing of passcodes. The Privilege Level 2 can change both the Level 1 and
2 passcodes, while Level 1 can only change the Level 1 passcode. Passcodes are four digit
numbers in the range 1000 to 9999. Type in the new passcode and press <Enter> to accept.
Asterisks are displayed instead of the numbers. <Clear> removes any digits typed. If no
digits are displayed, <Clear> returns to the Program or Passcode Menu.