EasyManua.ls Logo

Selve Commeo Control - Initial Operation Setup

Selve Commeo Control
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
GB
Installation
4.3. Initial operation
In order that the drive moves properly and can move to the interme-
diate position, the runtime of the connected drive has to bet set
during putting into operation!
Note: As long as the runtime has not been set, the extensions are
deactivated! Via the local operation on the device there is the possi-
bility of setting the runtime at that time!
4.3.1. Runtime setting
A one-time moving interruption when moving up and down as well as
an orange flashing status LED signalize the setting of the runtime.
Note: The runtime calculation for the commeo Control must be exe-
cuted without voltage interruption. When the voltage will be inter-
rupted during the setting, you must start over with the first step!
Operation Drive
or
Move the blind to the lower end posi tion
with the UP or DOWN button.
3 s
Press the STOP button of the transmitter for
3 seconds to save the lower end limit positi-
on.
or
Move to the upper end position.
3 s
Press the STOP button of the transmitter
for 3 seconds to save the upper end limit
position. Perform a test run.
Note: Alternatively the runtime setting can also be done with a com-
meo transmitter in the SELECT mode.

Table of Contents

Related product manuals