2
Interface box
Maintenance switch
Addendum to the Operating Instructions – MOVIPRO
®
– Accessories
10
The maintenance switch is used to interrupt the AC400V voltage supply to the inter-
face box. The maintenance switch can be secured with 3 locks. If the maintenance
switch is in position0, the MOVIPRO
®
is disconnected from the AC400V voltage sup-
ply.
Depending on the device type, the interface boxes are equipped with different main-
tenance switches:
• D.. disconnection switch
• M.. line and device protection
2.6.1 D.. disconnection switch
The following disconnection switches are possible, depending on the device's power
rating:
Power Short designation Description
Up to 7.5kW D02 Disconnection switch up to 16A
Up to 15kW D03 Disconnection switch up to 32A
Up to 22kW D04 Disconnection switch up to 42A
2.6.2 M.. line and device protection
The following line and device protection is possible depending on the power:
Power Short designation Description
Up to 2.2kW M13 Line and device protection up to 5A
Up to 4kW M14 Line and device protection up to 9A
Up to 7.5kW M16 Line and device protection up to 15A
23106913/EN – 02/2018