4 External braking resistors
4.1 Description
WARNING
Danger of electric shock due to high DC voltage in the supply lines (about
DC900V).
Severe or fatal injuries.
• Only use cables provided by SEW‑EURODRIVE.
• Install the cables according to the instructions.
WARNING
Risk of burns due to hot surfaces. Braking resistors reach a temperature of up to
250°C under load.
Serious injuries.
• Select a suitable installation location and observe the minimum clearance.
• Provide for covers to secure hot surfaces.
• Install the protection devices according to the regulations.
• Check the protection devices on a regular basis.
NOTICE
In case of incorrect assignment of the inverters, an overload may occur at the brak-
ing resistor and damage the braking resistor.
Damage to braking resistor.
• Observe the assignment of the braking resistor to the inverter and the project
planning guidelines.
For regenerative operation, an external braking resistor is connected to MOVIPRO
®
.
Observe the following technical data regarding the connection.
23106913/EN – 02/2018