EasyManua.ls Logo

SEW-Eurodrive PZM2xA-A075-D02-00 - Page 13

SEW-Eurodrive PZM2xA-A075-D02-00
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
Interface box
Electrical installation
Addendum to the Operating Instructions – MOVIPRO
®
– Accessories
13
2.8.3 Connection to MOVIPRO
®
Function
AC400V device supply output
DC24V output and input
With signal contact for maintenance switch
Connection type
Han-Modular
®
10 B, female
Connection image
C A
1 2
1
56
2
1
56
2
3
8
3
7
4
8
3
7
4
[a] Han
®
-C module, female
No. Name Function
1 L1 Supply system phase 1
2 L2 Supply system phase 2
3 L3 Supply system phase 3
[b] Han
®
-EE module, female
Coding of the device power, see chapter "Coding"(→214)
[c] Han
®
-EE module, female
No. Name Function
1 +24V_C DC24V input – backup voltage
2 SC Signal contact for maintenance switch
3 VO24 DC 24 V output
4 n.c. Not connected
5 0V24_C 0V24 reference potential – backup voltage
6 n.c. Not connected
7 GND Reference potential
8 n.c. Not connected
Hinged frame
No. Name Function
PE PE connection
23106913/EN – 02/2018