7. Measuring Range Codes
Select measuring range from the following table.
Note:Changing the code initializes all data related to measuring range.
Change setting with standby mode on 0-1 screen.
Input type Code Measuring range (°C) Measuring range (°F)
Universal-input
Thermocouple
B

*1 0 ~ 1800 °C 0 ~ 3300 °F
R

0 ~ 1700 °C 0 ~ 3100 °F
S

0 ~ 1700 °C 0 ~ 3100 °F
K

*2 -199.9 ~ 400.0 °C -300 ~ 750 °F

0.0 ~ 800.0 °C 0 ~ 1500 °F

0 ~ 1200 °C 0 ~ 2200 °F
E

0 ~ 700 °C 0 ~ 1300 °F
J

0 ~ 600 °C 0 ~ 1100 °F
T

*2 -199.9 ~ 200.0 °C -300 ~ 400 °F
N

0 ~ 1300 °C 0 ~ 2300 °F
PL *3

0 ~ 1300 °C 0 ~ 2300 °F
C(WRe5-26)

0 ~ 2300 °C 0 ~ 4200 °F
U *4

*2 -199.9 ~ 200.0 °C -300 ~ 400 °F
L *4

0 ~ 600 °C 0 ~ 1100 °F
Kelvin
K

*5
10.0 ~
350.0 K 10.0 ~ 350.0 K
AuFe-Cr

*6 0.0 ~ 350.0 K 0.0 ~ 350.0 K
K

*5 10 ~ 350 K 10 ~ 350 K
AuFe-Cr

*6 0 ~ 350 K 0 ~ 350 K
R.T.D
Pt100

-100.0 ~ 350.0 °C -150.0 ~ 650.0 °F

-200 ~
600 °C -300 ~ 1100 °F

-100.0 ~ 100.0 °C -150.0 ~ 200.0 °F

*7 - 50.0 ~ 50.0 °C -50.0 ~ 120.0 °F

0.0 ~ 200.0 °C 0.0 ~ 400.0 °F
JPt100

- 200 ~ 500 °C -300 ~ 1000 °F

- 100.0 ~ 100.0 °C -150.0 ~ 200.0 °F

*7 - 50.0 ~ 50.0 °C -50.0 ~ 120.0 °F

0.0
~ 200.0 °C 0.0 ~ 400.0 °F

-100.0 ~ 350.0 °C -150.0 ~ 650.0 °F
Pt100

-199.9 ~
550.0 °C -300 ~ 1000 °F

0.0
~ 350.0 °C 0.0 ~ 650.0 °F

0.0
~ 550.0 °C
0 ~ 1000 °F
JPt100

- 199.9 ~
500.0 °C -300 ~ 1000 °F

0.0
~ 350.0 °C 0.0 ~ 650.0 °F

0.0
~ 500.0 °C
0 ~ 1000 °F
mV
-10 ~ 10mV

Initial value: 0.0 ~ 100.0
Input scaling setting range: -1999 ~ 9999
 Span: 10 ~ 10,000 digit
Decimal point position: None, 1/2/3 digits following decimal point
Lower limit value is less than higher limit value.
NOTE:
If the difference between the higher limit value and lower limit value is less
than +10 digit or higher than +10,000 digit, the higher limit value is automatically
changed to + 10 digit or +10,000 digit.
The higher limit value cannot be set less than lower limit value +10 digit or
higher than +10,000 digit.
For current input, install input terminals of the specified receiving impedance (250
Ω) and use code 84 (0 ~ 20 mA) or 85 (4 ~ 20 mA).
0 ~ 10mV

0 ~ 20mV

0 ~ 50mV

10 ~ 50mV

0 ~ 100mV

Voltage
V
-1 ~ 1V

0 ~ 1V

0 ~ 2V

0 ~ 5V

1 ~ 5V

0 ~10V

Thermocouple: B, R, S, K, E, J, T, N, C: JIS/IEC R.T.D. Pt100: JIS/IEC JPt100
*1. Thermocouple B: Accuracy guarantee not applicable to 400°C (752°F) or below.
*2. Thermocouple K, T, U: Accuracy of those readings below -100°C is ± (0.7% FS + 1digit)
*3. Thermocouple PLII: Platinel
*4. Thermocouple U, L: DIN 43710
*5. Thermocouple K (Kelvin) accuracy *6. Thermocouple Metal-chromel (AuFe-Cr) (Kelvin) accuracy
10.0 ~ 30.0 K ± (2.0%FS + 40°C + 1digit) 0.0 ~ 30.0 K ± (0.7%FS + 6°C + 1digit)
30.0 ~ 70.0 K ± (1.0%FS +
14°C + 1digit) 30.0 ~ 70.0 K ± (0.5%FS + 3°C + 1digit)
70.0 ~ 170.0 K ± (0.7%FS +
6°C + 1digit) 70.0 ~ 170.0 K ± (0.3%FS + 2.C + 1digit)
170.0 ~ 270.0 K ± (0.5%FS +
3°C + 1digit) 170.0 ~ 280.0 K ± (0.3%FS + 2°C + 1digit)
270.0 ~ 350.0 K ± (0.3%FS +
2°C + 1digit) 280.0 ~ 350.0 K ± (0.5%FS + 2°C + 1digit)
*7. R.T.D. : accuracy is ± (0.3%FS + 1digit)
NOTE: Unless otherwise specified, the measuring range will be set as follows when shipped from the factory:
Input Standard/rating Measuring range
Multi inpu
t
K thermocouple 0.0 ~ 800.0°C
Voltage (V) 0 ~ 10V DC 0.0 ~ 100.0, no uni
t
