• Shinko protocol: , Modbus ASCII mode:
Modbus RTU mode:
Instrument number setting
• Sets individual instrument number to each DCL-33A when
connecting plural DCL-33As in serial communication.
• This item is not indicated when [Option: C5] is not added.
• Setting range: 0 to 95
0
Data transfer rate selection
• Selects data transfer rate in conformity with host computer
• This item is not indicated when [Option: C5] is not added.
• 2400bps:
, 4800bps: , 9600bps: , 19200bps:
9600bps
Parity selection
• Selects parity.
• This item is not indicated when [Option: C5] is not added or
when Shinko is selected in Communication protocol selection
• None:
, Even: , Odd:
Even
Stop bit selection
• Selects stop bit.
• This item is not indicated when [Option: C5] is not added or
when Shinko is selected in Communication protocol selection
• Setting: 1 or 2
1
5.5 Auxiliary function setting mode 2
Character Name, Description, Setting range Default value
Input type selection
• Selects a sensor type and temperature unit from thermocouple
(22 types), RTD (8 types), DC current (2 types) and DC voltage
(4 types).
• When changing input type from DC voltage input to the others,
detach the sensor connected to this unit before changing.
Input circuit will break down if input type is change while the
sensor is connected.
K
(-200 to 1370 )
K -200 to 1370 :
-199.9 to 400.0
:
J -200 to 1000
:
R 0 to 1760
:
S 0 to 1760
:
B 0 to 1820
:
E -200 to 800
:
T -199.9 to 400.0
:
N -200 to 1300
:
PL-
0 to 1390 :
C(W/Re5-26) 0 to 2315
:
Pt100 -199.9 to 850.0
:
JPt100 -199.9 to 500.0
:
Pt100 -200 to 850
:
JPt100 -200 to 500
:
K -320 to 2500 :
-199.9 to 750.0
:
J -320 to 1800
:
R 0 to 3200
:
S 0 to 3200
:
B 0 to 3300
:
E -320 to 1500
:
T -199.9 to 750.0
:
N -320 to 2300
:
PL-
0 to 2500 :
C (W/Re5-26) 0 to 4200 :
Pt100 -199.9 to 999.9 :
JPt100 -199.9 to 900.0
:
Pt100 -300 to 1500
:
JPt100 -300 to 900
:
4 to 20mA -1999 to 9999 :
0 to 20mA -1999 to 9999 :
0 to 1V -1999 to 9999 :
0 to 5V -1999 to 9999 :
1 to 5V -1999 to 9999 :
0 to 10V -1999 to 9999 :
Scaling high limit setting
• Sets the scaling high limit value.
• Scaling low limit setting value to Input range high limit value
(For DC voltage and current inputs, decimal point place follows
the selection.)
1370
Scaling low limit setting
• Sets the scaling low limit value.
• Input range low limit value to scaling high limit setting value
-200