15
Insulation resistance : 10M or more, at 500V DC
Dielectric strength : 1.5kV AC for 1minute between input terminal and power terminal
1.5kV AC for 1minute between output terminal and power terminal
Supply voltage : 100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz
Allowable voltage fluctuation: 100 to 240V AC: 85 to 264V AC, 24V AC/DC: 20 to 28V AC/DC
Power consumption : Approx. 8VA
Ambient temperature : 0 to 50 (32 to 122 )
Ambient humidity : 35 to 85%RH (no condensation)
Weight : Approx. 200g
External dimensions : 48 x 48 x 95mm (W x H x D)
Material : Flame-resistant resin (Case)
Color : Light gray (Case)
Attached functions : [Set value lock], [Sensor correction], [Auto/manual control selection],
[Input abnormality indication]
Output status
selection
when input
abnormal (*1)
Overscale
Measured value
has exceeded
Indication range
high limit value.
" " flashes.
ON (20mA) or
OUT1 high
limit value (*2)
OFF (4mA) or
OUT1 low limit
value
OFF or
OUT2 low limit
value
ON or
OUT2 high limit
value (*2)
OFF (4mA) or
OUT1 low
limit value
OFF or
OUT2 low limit
value
Underscale
Measured value
has dropped below
Indication range low
limit value.
" " flashes.
OFF (4mA) or
OUT1 low
limit value
ON (20mA) or
OUT1 high limit
value (*2)
ON or
OUT2 high limit
value (*2)
OFF or
OUT2 low limit
value
OFF (4mA) or
OUT1 low limit
value
OFF or
OUT2 low limit
value
(*1) This is only available for DC input and when OUT1 is DC current output type.
If OUT1 is not DC current output, the output status will be the same one as when is selected
during “Output status selection when input abnormal”.
For manual control, the preset manipulated variable (MV) is outputted.
(*2) Outputs a value between OFF (4mA) and ON (20mA) or between OUT1 (or OUT2) low limit value
and OUT1 (or OUT2) high limit value, depending on deviation.
Thermocouple, RTD input
Indication range and Control range for thermocouple inputs other than the above:
Input range low limit value –50 (100 ) to Input range high limit value +50 (100 )
DC input
Indication range: [Scaling low limit value–Scaling span x 1%] to [Scaling high limit value +Scaling span x 10%]
However, “ ” or “ ” flashes when a range of –1999 to 9999 is exceeded.
Control range: [Scaling low limit value–Scaling span x 1%] to [Scaling high limit value +Scaling span x 10%]
DC input disconnection
When DC input is disconnected, PV display flashes “ ” for 4 to 20mA DC and 1 to 5V DC inputs, and
“ ” for 0 to 1V DC input.
For 0 to 20mA DC, 0 to 5V DC and 0 to 10V DC inputs, the PV display indicates the value corresponding with
0mA or 0V input.