Important information
DANGER
H
azard due to lack of effectiveness of the protective device
Systems of safety light curtains that operate in close proximity to each other can inter‐
fere with each other.
b
Use appropriate measures to prevent systems in close proximity from interfering
with each other.
4.3.4.1 Using reversed direction of transmission
Using reversed direction of transmission
T
he direction of transmission of the system " can be changed during mounting by
switching the positions of the sender and receiver. With reversed direction of mounting,
the receiver " is not affected by the infrared light from the sender !.
"
!
s
s
s
s
s
s
s
s
s
s
s
s
s
s
rs
r
Figure 13: Trouble-free operation due to reversed direction of transmission of system
1
and sys‐
tem
2
4.4 Integration in electrical control
Overview
T
his chapter contains important information about integration in the electrical control.
Information about the individual steps for electrical installation of the device: see "Elec‐
trical installation", page 43.
Requirements for use
The output signals of the protective device must be analyzed by downstream controllers
in such a way that the dangerous state of the machine is ended safely. Depending on
the safety concept, the signal is analyzed by safety relays or a safety controller, for
example.
DANGER
H
azard due to lack of effectiveness of the protective device
In the case of non-compliance, it is possible that the dangerous state of the machine
may not be stopped or not stopped in a timely manner.
b
Make sure that the following control and electrical requirements are met so that
the safety light curtain can fulfill its protective function.
It mus
t be possible to electrically influence the control of the machine.
The electrical control of the machine must meet the requirements of IEC 60204-1.
A restart interlock must be implemented depending on applicable national regula‐
tions or required reliability of the safety function. Because the safety light curtain
4 P
ROJECT PLANNING
22
O P E R A T I N G I N S T R U C T I O N S | deTec4 Core Ex 8017023/14Q6/2020-04-27 | SICK
Subject to change without notice