Teach in the current distance as a single or DtO switching point for Q
1
in the menu
Operating example or steps:
RUN mode
→ Q
1
Output
→ ModeQ
1
/ to → Teach Q
1
→ Q
1
Position object
→ Saved
to → RUN mode
Necessary default settings:
Factory setting or mode Q
1
= DtO (1
point)
Factory setting:
30,000 mm
Teach in the current distance as an inverted single or DtO switching point for Q
1
in the menu
Operating example or steps:
RUN mode
→ Q
1
Output
→ ModeQ
1
/ to → Teach Q
1
→ Q
1
/ to → Q
1
not
Position object
→ Saved
to → RUN mode
Necessary default settings:
Factory setting or mode Q
1
= DtO (1
point)
Factory setting:
-
Manually teach in the desired distance as a single or DtO switching point for Q
1
Operating example or steps:
RUN mode
→ Q
1
Output
→ ModeQ
1
/ to → Manual Q
1
→ Q
1
→ 30000 (Note: 3 = flashing 3)
/ , / , / , / ,
/ → desired distance in mm
→ Saved
to → RUN mode
Necessary default settings:
Factory setting or mode Q
1
= DtO (1
point)
Factory setting:
30,000 mm
OPERATION 6
8017154/1AVV/2021-03-24 | SICK O P E R A T I N G I N S T R U C T I O N S | DT50-2 Pro
25