GENIUS 2.2 PANIC, Electromechanical mul-point lock
8 
In accordance with DIN EN 179 and DIN EN 1125, tesng and maintenance of the GENIUS 2.2 PANIC mul-point
lock must be conducted aer 20,000 opening cycles, and once a month at least. The results must be documented.
Immediate tesng and maintenance must be conducted in the
case of vandalism.
 
  
Check whether supplementary locking systems
have been subsequently added.
Check whether original components of the
GENIUS 2.2 PANIC mul-point lock have been
replaced.
If supplementary locking systems have been
added, the
GENIUS 2.2 PANIC mul-point lock will not func-
on as intended.
If the components of the GENIUS 2.2 PANIC mul-
-point lock deviate from the originally delivered/
approved components, the GENIUS 2.2 PANIC
mul-point lock will not funcon as intended.
In both these cases, the delivery status must be
restored immediately otherwise the warranty will
expire.
Get in touch with your contractual partner.
 
  
Check that all cables are free of damage.
Check that all plug connecons are free from
contaminaon , corrosion or any form of
damage and that all cable connectors are rmly
seated in the bushing.
Damaged cables and contaminated, corroded or
loose plug connecons can lead to malfuncon/
failure.
Damaged cables and plug connecons must be
replaced immediately.
Get in touch with your contractual partner.
 
  
Check that the screw connecons of the oper-
ang elements (lever handle or push bar) are
ghtened and the operang elements operate
free of play.
Check that all further screw connecons of the
GENIUS 2.2 PANIC mul-point lock are rmly
ghtened.
When the screw connecon is loosened, the GE-
NIUS 2.2 PANIC mul-point lock works imprecisely,
the wear and tear increases, potenally resulng
in malfuncon/failure.
Tighten all loosened screws (manually, max. 1
Nm).
If the screws can no longer be ghtened (e. g.
because they have been overghtened), the screw
connecon must be serviced immediately.
Get in touch with your contractual partner.
 
  
With the door open, bring the locking elements
into the locking posion and check the hardware.
e. g.:
- Deformaon
- Wear
- Breakage
Damaged locking elements could inhibit/prevent
the locking and release and damage the PVC back-
ing of the frame parts.
The GENIUS 2.2 PANIC mul-point lock must be
replaced if the locking elements are damaged.
Get in touch with your contractual partner.
 
  
Check frame parts for dirt, foreign objects and
damage
Dirty, blocked or damaged frame parts obstruct or
prevent the locking and release. This will lead to
malfuncon/ failure.
Clean the frame parts and check the funconing
once again. The frame parts must be replaced if
the faultless funcon cannot be restored.
Damaged frame parts must be replaced on
principle.
Get in touch with your contractual partner.