5 – 10 3ZW1012-0WL11-0AB1
5.2.5 Permissible connection bar versions for frame
size I 1000 V DC non-automatic air circuit breaker
Frame size I 1000V DC non-automatic air circuit breakers are only
available in the 4-pole version. The upper connections of phases N
and L3 form the positive/negative poles in a non-automatic air cir-
cuit breaker that is switched in series. Horizontal and vertical con-
nections are available. The six remaining horizontal connections
must be connected according to the schematics below.
5.2.6 Permissible connections, connection schemes for frame
size I 1000 V DC non-automatic air circuit breaker
5.2.5 Zulässige Anschlussschienen-Varianten für
Baugröße I 1000 V DC Leistungstrennschalter
Baugröße I 1000 V DC Leistungstrennschalter werden nur in vier-
poliger Ausführung angeboten. Plus-/Minuspol des in Reihe zu ver-
schaltenden Leistungstrennschalters bilden die außenliegenden
jeweils oberen Anschlüsse der Phasen N und L3. Verfügbare Schie-
nenvarianten für diese beiden Anschlüsse sind Horizontal- und Ver-
tikalanschluss. Die sechs verbleibenden Horizontalanschlüsse sind
nach folgenden Schemata zu verschalten.
5.2.6 Zulässige Verschaltungen, Schaltpläne für
Baugröße I 1000 V DC Leistungstrennschalter
Hinweis Note
Minimale Anforderung an die Kurzschlussbrücken
(Anzahl x Breite x Dicke):
3x50mmx10mm
Minimum requirement on the jumpers
(quantity x width x thickness)
3x50mmx10mm