Siemens PM240-2_EN_rev00-30082019.docx    11-5 
= parameter has no effect 
•  Setting the STOP UPWARD 
 Preferably adjust only the parameters visible in the list User. Some of parameters mentioned are 
available only after contacted OMARLIFT Support. 
The slowdown starts  when  you remove the command HIGH  SPEED, and  the UPWARDS command 
remains activated; once the elevator get on the floor, you will take off the UP command and the engine 
is automatically set to zero speed. 
To achieve the desired accuracy of the stop, adjust the parameters P21512 (2.2.7) (Low Speed) and 
P21513 (2.2.14) (Deceleration Final). 
EXCESSIVE 
LENGTH  OF 
LOW-SPEED  
ARRIVAL  AT 
THE  FLOOR 
WITHOUT  LOW 
SPEED 
PRESENCE  OF 
LOW SPEED, BUT 
STOP  BEYOND 
THE FLOOR 
PRESENCE  OF 
LOW  SPEED,  BUT 
STOP  BEFORE 
THE FLOOR 
The stopping accuracy should not be affected too much by the load in the cabin or oil temperature, as 
have been calculated with the appropriate automatic compensation. 
If the situation on the arrival on the floor isn’t satisfactory modifying the load or temperature, proceed as 
follows: 
-  Adjust  the  stop  with  cold  oil  and  empty  car,  acting  on  the  parameters  P21512  (2.2.7)  and  P21513 
(2.2.14). 
-  Repeat the test at the same temperature, but at full load and if necessary to adjust the accuracy of the 
correct destination, this time to act on the parameter PX8 (DO NOT CHANGE the parameters P21512 
(2.2.7) and P21513 (2.2.14)!) 
-  Make several trips to heat the oil, oil heat control the stopping accuracy. If the car stops before the 
floor, modify the parameter PX2 until you have the desired accuracy. 
-  Finally, check with cold oil and empty car that stopping accuracy remained the one obtained with the 
initial tests, otherwise repeat the procedure.