Siemens PM240-2_EN_rev00-30082019.docx    11-7 
The  P21630  parameter  set  the  increase  of  speed  in  respect  to  the  low  speed  in  downward  direction 
(negative value)  in order to obtain a motor rotation in contrary sense  during the  valve closing phase. To 
modify  this  parameter  you  have to  proceed  step  by  step  of  0,05  at  each  time.  For  the  compensation  of 
P21630 when the temperature changes, contact the OMARLIFT support. 
 
ALWAYS CHANGE ONLY ONE PARAMETER AT A TIME. 
11.4.3 Re-leveling 
•  Setting the re-leveling 
Test the re-leveling at empty conditions, moving the elevator downwards/upwards in respect to the 
floor, by press  the Emergency button for  descent  direction,  and  with the hand  pump for upwards 
direction. 
If the restoration of the position of the plan is not satisfactory, adjust the parameter P21515 (2.2.8) 
until you get the desired stop. 
You can change the re-leveling at full load using the parameter PX9. 
You can change the re-leveling at maximum oil temperature, using the parameter PX3. 
11.4.4 Emergency 
•  Parameters for EMERGENCY operation (input X121.7) 
The inverter SIEMENS allows the dedicated management of a state of emergency power supply by 
installing a UPS AC 400 V (not supplied), whose installation and dimensioning are the responsibility 
of the customer. 
The operation via UPS unit guarantees a limited number of runs both uphill and downhill, dependent 
on the dimensioning of the same. 
The Emergency function is controlled via input X121.7 
You can adjust the speed of movement in the direction up or down through the parameters: 
P21546 (2.6.1)    Emergency Speed Upward 
P21547 (2.6.2)    Emergency Speed Downward 
11.4.5 General Considerations 
•  General rules for proper adjustment 
-  If the high-speed cabin speed is not constant, check the motor data. In particular, the motor data 
must match the "real"  situation.  Also  verify that the  mechanical devices (cabin / piston) have 
uniform friction during movement. 
-  To have a stop  with constant  precision is necessary that  the  cabin tread a small space (5 ÷ 
10cm) in low constant speed (adjust the parameters as indicated in the table). 
-  Set the low speed to the desired value, bearing in mind that a very low value increases the time 
of arrival at the floor. 
-  Do not adjust the switching frequency at too high values, otherwise the engine and the inverter 
will overheat unnecessarily. 
11.5  RUPTURE VALVE TEST 
The rupture valve test, verify the functionality of the safety device, that normally is installed on the cylinder or 
in it neighborhood. This safety device, should stop the elevator in case of speed exceeding for 30% the rated 
speed of the elevator. 
SIEMENS inverter supplied by OMARLIFT, allows to test the functionality by a specific function, that you can 
use only to perform the test and verify the rupture valve intervention. 
If you need to perform a rupture valve test, see the following steps: 
•  Make sure that the system is on safety conditions (travel shaft free, functionality of all safety and 
control devices of elevator, etc..) 
•  Load the elevator to the nominal weight, and climb to the top floor 
•  Activate the test function, by setting the inverter parameter P21523 Parachute function (2.13.1) to 
the value 1