Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
121
measured as a percentage of the differ-
ence between High Calibration Point and
High Calibration Point
Sensor reference point measured as a percentage of Low Cali-
converts a level measurement to a volume output
a)
allows
to be set to a user-defined value
Current Output Function must be set to
before modifying
mA Output Value (2.6.6.).
Re-
member to restore the previous Current Output Function setting after modifying mA Output Value.
To view the mA reading in the secondary region of the LCD, press on the handheld
programmer.
To modify Current Output Function via SIMATIC PDM:
● Open the menu Device – Select Analog Output. See Select Analog Output via SIMATIC
PDM (Page 84) for more detail.
4 mA Setpoint (2.6.2.)
Sets the process level corresponding to the 4 mA value. 4 mA always defaults to 0, and
Current Output Function (2.6.1.) determines whether this is a Level, Space, Distance, or
Volume measurement. (See
Current Output Function (2.6.1.) for an illustration.)
Range: –999999 to +999999 (limits vary with current function and units)
Default:
m (set to value corresponding to 0% as defined by Current
Current Output Function (2.6.1.)
● Enter the reading that is to correspond to a 4 mA output.
●
Units are defined in Units (2.2.1.) for Level, Space, or Distance. Units are unspecified for
Volume.
20 mA Setpoint (2.6.3.)
Sets the process level corresponding to the 20 mA value. 20 mA always defaults to 100%,
and
Current Output Function (2.6.1.) determines whether this is a Level, Space, or Distance
measurement. (See
Current Output Function (2.6.1.) for an illustration.)
Range: –999999 to +999999 (limits vary with current function and units)
Default:
m (set to value corresponding to 100% as defined by Current
Units (2.2.1.)
Current Output Function (2.6.1.)
● Enter the reading that is to correspond to a 20 mA output.
●
Units are defined in Units (2.2.1.) for Level, Space, or Distance. Units are unspecified for
Volume.