Commissioning
6.3 Application examples
SITRANS LR250 with mA/HART
64 Operating Instructions, 10/2019, A5E32220602-AG
Sensor reference point
5 m
High calibration point
Low calibration point
0.5 m
0% level
100% level
Parameter type
Parameter No. /Name
Options/
Values
Function
Quick Start
Wizard parame-
ters
Introduction
NEXT
Continue with Wizard.
Language
NEXT
Continue with current language.
Material
LIQUID
Response Rate
MED
Medium =1 m/minute
Units
M
meters
Operation
LEVEL
Level
Low Calibration Point
5
5 m (16.5 ft)
High Calibration Point
0.5
0.5 m (1.64 ft)
Wizard Complete
FINISH
Transfers Quick Start settings to
device.
Independent
parameters
LOE Timer (2.5.2.)
2
2 minutes
Material Level (2.5.1.)
HI
Fail-safe level set to High
Return to Measurement: press Mode to start normal operation.