Remote operation
7.2 Operating via AMS Device Manager
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
95
Quick Start
Step 1 Identification
1. Navigate to Configure/Setup > Wizard > Quick Start.
2. Click on Step 1.
3. You can accept the default values without modification. (Description, Message, and
Installation Date fields can be left blank.) If desired, make changes then click on
Apply.
Step 2 Application
1. Click on Step 2.
2. Select the application type (Level/vessel, Level/stillpipe, Level/bypass pipe,
Volume/vessel, Volume/stillpipe, or Volume/bypass pipe) and the material (Liquid or Low
dielectric liquid).
3. Click on Apply.
Step 3 Vessel Shape
1. Click on Step 3.
2. Select a predefined vessel shape. To describe a more complex shape see Linearization
(Page 96).
3. Click on Apply.
Step 4 Ranges
1. Click on Step 4.
2. Change units if desired (in meters by default).
3. Set High and Low Calibration points.
4. To convert the reading from level to volume enter a value for Maximum Volume.