Appendix 7SV512 v1
C53000-G1176-C91 121
Table C.2 Table of All Binary Outputs 7SV512
Rel,LED
To Output Relay or LED
R
Annunc. marshallable
OP, PC
To operator panel or PC
K
Annunciated "Coming"
K/G
"Coming" and "Going"
LSA
To localized substation autom
K
Annunciated "Coming"
K/G
"Coming" and "Going"
FNo Abbreviation Meaning
Rel
LED
OP
PC LSA
1 not allocated no annunciation function allocated R
5 >Time Synchro synchronize internal real time clock R
6 >LED reset reset stored LED indicators R
7 >Start FltRec start fault recording R K
16 >CB Aux. L1 circuit breaker aux. contact: Phase L1 R K/G
17 >CB Aux. L2 circuit breaker aux. contact: Phase L2 R K/G
18 >CB Aux. L3 circuit breaker aux. contact: Phase L3 R K/G
19 >CB Aux. 3p C CB aux. contact: all poles closed R K/G
20 >CB Aux. 1p C CB aux. contact: any pole closed R K/G
21 >Annunc. 1 user defined annunciation 1 R K/G K/G
22 >Annunc. 2 user defined annunciation 2 R K/G K/G
23 >Annunc. 3 user defined annunciation 3 R K/G K/G
24 >Annunc. 4 user defined annunciation 4 R K/G K/G
31 >B/F on switch on breaker failure protection R
32 >B/F off switch off breaker failure protection R
33 >Pol.Dis. on switch on pole discrepancy supervision R
34 >Pol.Dis. off switch off pole discrepancy supervis'n R
35 >Flt.Rec. on switch on fault recording function R
36 >Flt.Rec. off switch off fault recording function R
59 >ParamSelec.1 parameter set selection 1 (with 60) R
60 >ParamSelec.2 parameter set selection 2 (with 59) R
70 >Start fault detection from feeder protection R K/G K/G
71 >Start N earth fault detection from feeder prot R K/G K/G
72 >Trip general trip command from feeder prot. R K/G K/G
73 >Trip 3pole 3-pole trip from feeder protection R K/G K/G
74 >Trip L1 trip phase L1 from feeder protection R K/G K/G
75 >Trip L2 trip phase L2 from feeder protection R K/G K/G
76 >Trip L3 trip phase L3 from feeder protection R K/G K/G
77 >B/F block block breaker failure protection R K/G K/G
78 >CB defect circuit breaker defective (can't trip) R K/G K/G