7SV512 v1 Appendix
122 C53000-G1176-C91
FNo Abbreviation Meaning
Rel
LED
OP
PC LSA
101 Dev.Operative Device operative R K/G
102 Re-start Re-start of processor system K K
103 Syst.Flt Fault in the Power System K K
104 Fault Fault event K
106 LED reset LED's Reset K
107 Flt.Rec.activ Fault recording data being transmitted R
108 Fault.Rec.off Fault recording function switched off R K/G
109 Rel.TimeResp. Real time response to LSA K
110 Param.Running Parameters are being set R K/G
116 Param. Set A Parameter set A is active R K/G K/G
117 Param. Set B Parameter set B is active R K/G K/G
118 Param. Set C Parameter set C is active R K/G K/G
119 Param. Set D Parameter set D is active R K/G K/G
121 Failure 18V Failure of internal 18Vdc power supply R K/G K/G
122 Failure 15V Failure of internal 15VDC power supply R K/G K/G
123 Failure 5V Failure of internal 5VDC power supply R K/G K/G
124 Failure 0V Failure of internal 0VDC power supply R K/G K/G
125 Failure RKA Command relay supervision alarm R K/G K/G
131 Annunc. Lost Annunciations lost due to buffer overf K K
132 Fault Bff.Ovr Fault annunciation buffer overflow
134 Annu.LSA Lost Annunciations for LSA lost K
135 FaultFlagOver Fault flag buffer overflow K
136 Oper.Ann.Inv Operational annunciations invalid K
137 Fault Ann.Inv Fault annunciations invalid K
138 Annunc.Inval. Alarm not valid K/G
139 Stat.Buff.Inv Statistic annunciation buffer invalid K/G
140 LED Buff.Inva LED annunciation buffer invalid K/G
151 Failure äI Failure: current summation supervisio R K/G K/G
154 Failure Isymm Failure: current symmetry supervision R K/G K/G
161 Chs Error Error in check sum K/G
162 Chs.1 Error Error in check sum for parameter set A K/G
163 Chs.2 Error Error in check sum for parameter set B K/G
164 Chs.3 Error Error in check sum for parameter set C K/G
165 Chs.4 Error Error in check sum for parameter set D K/G
469 Device FltDet General fault detection of device R K
470 Device Trip General trip of device R
471 BFP off Breaker fail protection is OFF R K/G K/G
472 BFP-Pickup Breaker fail protection initiated R K/G K/G
473 BFP-Start Breaker fail protection started R K K/G
www . ElectricalPartManuals . com

Table of Contents