EasyManuals Logo

Siemens 8DA10 Series User Manual

Siemens 8DA10 Series
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #190 background imageLoading...
Page #190 background image
Operation
190/214 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
Emergency operation of
the DISCONNECTING
function
If the switch does not reach its end position, e.g., due to a failure of the auxiliary voltage
during disconnector operation, push the operating lever with pushed-on adapter onto the
hexagonal shaft for the DISCONNECTING function in such a way that the pin of the hexagonal
shaft fits in the inner slot of the operating adapter.
Fig. 200: Inserting the operating lever with pushed-on adapter (DISCONNECTING function)
Fig. 201: Emergency operation of the DISCONNECTING function of the three-position
disconnector
Push the interrogation lever downwards.
Push the control gate to the left.
The opening for the DISCONNECTING function is free.
To switch the DISCONNECTING function of three-position disconnector to the desired end
position (CLOSED or OPEN), perform the following actions:
Turn the emergency operating lever until the position indicator changes to CLOSED or OPEN
position.
Remove the emergency operating lever again.
The control gate returns to its initial position.
The opening for the DISCONNECTING function is closed.
Check the correct end position of the operating shaft with the standard operating lever.
Position of emergency
operating lever
Marking of slot Position of three-position
disconnector
horizontal bottom CLOSED
top OPEN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 8DA10 Series and is the answer not in the manual?

Siemens 8DA10 Series Specifications

General IconGeneral
BrandSiemens
Model8DA10 Series
CategoryCircuit breakers
LanguageEnglish

Related product manuals