Storage in closed rooms The following switchgear parts must be stored in closed rooms:
Unpacked parts
Transport units which are not packed in seaworthy crates
The storage room should have the following characteristics:
Well-ventilated
Free of dust
Dry and protected against flooding
The relative humidity should not exceed 50%
Protected against vermin (e.g. insects, mice, rats)
Even floor to enable stable storage
Floor with adequate load-bearing capacity
Sufficient size to enable clearly arranged storage
Do not unpack small parts to avoid corrosion and loss.
Store transport units in such a way that they can be taken out later in the correct order for
installation.
Provide for sufficient ventilation in heated storage rooms.
Check transport units for condensation every 4 weeks.
If the inside of the packing or parts of the switchgear show condensation:
Remove the packing, dry the switchgear and the packing. Then, re-pack the switchgear.
Outdoor storage The storage place must have the following characteristics:
Protected against rain water
Protected against flooding as well as melting water from snow and ice
Protected against pollution and vermin (e.g., insects, mice, rats)
Even floor to enable stable storage
Floor with adequate load-bearing capacity
Sufficient size to enable clearly arranged storage
Place transport units on planks or square timber for protection against floor humidity.
Store transport units in such a way that they can be taken out later in the correct order for
installation.
After 6 months (12 months with seaworthy long-time packing) of storage, unpack the
transport units and store them in closed rooms, or regenerate the seaworthy packing
(see below).
Regenerating the
seaworthy packing
After 6 months (12 months with seaworthy long-time packing) of storage, the protection of
the seaworthy packing is exhausted. If the transport units still need to be stored outdoors,
the seaworthy packing must be regenerated.
If there is no sufficient knowledge about professional regeneration of the packing:
Ask for expert personnel via the competent Siemens representative.
➭Open the packings.
Replace the desiccant bags by the same number of new desiccant bags.
Pack the switchgear so as to reach full protection:
Heat-seal the PE films hermetically tight and rebuild the seaworthy crates completely.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 8DA10 Series and is the answer not in the manual?

Siemens 8DA10 Series Specifications

General IconGeneral
BrandSiemens
Model8DA10 Series
CategoryCircuit breakers
LanguageEnglish

Related product manuals