Alarms and alerts 9410 series
5. Click Setup. The Alarm Learning Setup screen is displayed. Configure the
learning parameters.
Click Start to begin sag/swell learning. Click Abort to stop learning.
6. Apply the learned sag/swell limits.
Automatic: the limits are automatically applied unless there are issues with the
learning process.
Manual: navigate to Power quality > Sag/Swell. Select the Swell limit % or
Sag limit % and click Learn. Click Install to apply the learned limits.
NOTE: If you click Install while learning is in progress (in either manual or
automatic installation mode), it stops the learning process and prompts you for
confirmation that you want to stop learning and install the learned limits. Once you
have confirmed, the learned limits are automatically installed or prepared for
manual installation.
Parameter Value/Range Description
Install mode Automatic,
Manual
Automatic: the learned values are automatically
applied.
Manual: the learned values are stored for you to review
and enter.
Duration 1-365 Days for maximum learning duration.
Configuring digital input alarms using ION Setup
You can use ION Setup to configure the digital alarm settings.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Alarming > Digital Input.
4. Configure the digital input alarm settings by selecting an input and clicking Edit.
Some settings are not configurable and are grayed out.
5. Click Save to save the changes to the meter.
Parameter Value/Range Description
Input Input On/Input Off Specifies the input state/alarm behavior:
Input On: the alarm is on when the digital input is on.
Input Off: the alarm is on when the digital input is off.
Force Off Checked/Unchecked Forcing the alarm off disables all functions of the associated input.
To stop an alarm from being displayed without affecting digital input features, set the
alarm priority to Info Only.
Label String value When available, lets you modify the default label so it more clearly identifies the
alarm. Letters, numbers, and underscores are permitted. Spaces are not permitted.
Alarm Priority None, Info Only, Low,
Medium or High
Specifies the priority level of the digital input alarm. To disable the alarm, set priority
to Info Only.
Custom Priority 0-255 Select custom priority to view and configure the event priority of the event associated
with the alarm. The event log cutoff value is displayed for reference; event priorities
above the cutoff are stored in the meter’s event log.